DocumentCode :
3399346
Title :
Compression connector performance on oxidized aluminum cable conductors
Author :
Dang, Chinh ; Pélissou, Serge ; St-Antoine, Serge ; Savage, Richard ; Côté, Jacques
Author_Institution :
Res. Inst. of Hydro-Quebec, Varennes, QC
fYear :
2008
fDate :
21-24 April 2008
Firstpage :
1
Lastpage :
4
Abstract :
Oxidized aluminum conductors are often found in overhead and underground distribution systems. Jointing these oxidized aluminum conductors with compression connectors in cable joints can lead to thermal runaway and fire hazard as found in our laboratory experiments. This problem was partly alleviated by the clearing and degreasing processes used in the rejuvenation of the underground cable insulation by silicone injection. It can, however, be eliminated by chemical cleaning.
Keywords :
power cable insulation; chemical cleaning; compression connector; fire hazard; overhead distribution systems; oxidized aluminum cable conductors; silicone injection; thermal runaway; underground cable insulation; underground distribution systems; Aluminum; Cable insulation; Chemical hazards; Cleaning; Conductors; Connectors; Fires; Power cable insulation; Power cables; Thermal conductivity; Aluminum conductors; compression connectors; oxidation;