Abstract :
In this paper, a simplified test method has been proposed and implemented for evaluating the thermal interruption capability of the power circuit breakers. It has been shown that the thermal interruption limit of the circuit breaker can be evaluated in a more accurate way using the proposed method in comparison to the conventional synthetic test methods due to the avoiding the influences of the arc voltage. To validate the proposed test circuit, a series of experiments have been carried out on a 24 kV SF6 gas circuit breaker with rated short circuit of 25 kA and the successful interruption zone in terms of the time derivative of the current before current zero (di/dt) and rate of rise of recovery voltage (dv/dt) has been determined. The experimental results are in good accordance with the theoretical model predictions.
Keywords :
SF6 insulation; circuit breakers; circuit-breaking arcs; SF6 gas circuit breaker; accurate evaluation method; arc voltage; conventional synthetic test methods; current 25 kA; power circuit breakers; thermal interruption; voltage 24 kV; Circuit breakers; Circuit testing; Plasma applications; Plasma density; Power system modeling; Predictive models; Sulfur hexafluoride; System testing; Thermal conductivity; Voltage; Circuit breakers; interruption capability test; synthetic test; thermal re-ignitions;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Transmission and Distribution Conference and Exposition, 2008. T&D. IEEE/PES
Conference_Location :
Chicago, IL
Print_ISBN :
978-1-4244-1903-6
Electronic_ISBN :
978-1-4244-1904-3
Type :
conf
DOI :
10.1109/TDC.2008.4517238
Filename :
4517238
Link To Document :
بازگشت