Title :
Measurement of the dielectric properties of paper-oil cables and the cellulose-oil insulation system of power transformers
Author :
Menzel, Johannes ; Patsch, Rainer ; Kamenka, Dieter
Author_Institution :
Inst. of Mater. & Diagnostics in Electr. Eng., Univ. of Siegen, Siegen, Germany
Abstract :
Return Voltage Measurements are an efficient tool to measure the dielectric properties of an insulating system and thus to characterize the degradation of cellulose-oil insulations. They are widely used for the diagnosis of power cables. As a consequence of misinterpretations of the results in the past, the use Return Voltage Measurements for power transformers has been reduced. Nevertheless - performing a physically meaningful interpretation of the measured curves - the application on power transformers is also very promising, especially because the geometry of the insulation system in a power transformer is closer to the conditions described by the Maxwell model for two dielectrics in series. Return Voltage curves for new or not severely aged transformers fit very well the type and shape of the voltage curve predicted by the Maxwell equivalent circuit. Ageing and degradation phenomena in the oil and the paper lead to a deviation from this behaviour.
Keywords :
dielectric measurement; power cables; power transformer insulation; Maxwell equivalent circuit; cellulose-oil insulation system; dielectric properties; paper-oil cables; power transformers; return voltage measurements; Aging; Cable insulation; Degradation; Dielectric measurements; Dielectrics and electrical insulation; Power cables; Power measurement; Power transformer insulation; Power transformers; Voltage measurement; Cellulose-oil insulation; boundary polari-zation; dielectric time constants;
Conference_Titel :
Properties and Applications of Dielectric Materials, 2009. ICPADM 2009. IEEE 9th International Conference on the
Conference_Location :
Harbin
Print_ISBN :
978-1-4244-4367-3
Electronic_ISBN :
978-1-4244-4368-0
DOI :
10.1109/ICPADM.2009.5252441