DocumentCode :
3399773
Title :
Electrical performance of fiberglass crossarm in distribution and transmission lines
Author :
Grzybowski, S. ; Disyadej, T.
Author_Institution :
Dept. of Electr. & Comput. Eng., Mississippi State Univ., Starkville, MS
fYear :
2008
fDate :
21-24 April 2008
Firstpage :
1
Lastpage :
5
Abstract :
An investigation of the electrical performance of the fiberglass crossarm for distribution and transmission lines is presented. This paper shows data from fiberglass crossarms obtained at the Mississippi State University High Voltage Laboratory as based on the AC voltage and the CFO voltage under dry and wet condition. The structure and electrical properties are briefly explained. Different lengths of the fiberglass crossarm were tested, and their electrical performances are demonstrated. According to the test results, the fiberglass crossarm cannot be used as a single component in the insulation system. It has to be installed with insulators as a multi-insulation system to improve the lightning insulation strength of distribution and transmission lines. With advantages, fiberglass crossarm can be used in place of wood crossarm.
Keywords :
glass fibres; poles and towers; power distribution lines; power transmission lines; critical flashover voltage; distribution lines; fiberglass crossarm; lightning insulation strength; transmission lines; Conducting materials; Dielectrics and electrical insulation; Lightning; Mechanical factors; Optical fiber testing; Plastics; Power transmission lines; Steel; Transmission lines; Voltage; Critical flashover voltage; distribution line; fiberglass crossarm; transmission line; wood crossarm;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Transmission and Distribution Conference and Exposition, 2008. T&D. IEEE/PES
Conference_Location :
Chicago, IL
Print_ISBN :
978-1-4244-1903-6
Electronic_ISBN :
978-1-4244-1904-3
Type :
conf
DOI :
10.1109/TDC.2008.4517257
Filename :
4517257
Link To Document :
بازگشت