This paper presents results of an integrated condition monitoring of a power transformer. The main concern is that the equipment produces unusual vibration and noise, which is significantly higher than those initiated by similar type of transformers operated in the region. Several condition monitoring techniques were applied to the transformer including vibration and partial discharge measurements. The measurement results indicated that the transformer initiates a high level of vibration at twice power frequency. Similar indication was also discovered from measured partial discharge data.
Keywords :
condition monitoring; partial discharge measurement; power transformers; vibrations; condition monitoring; noise; partial discharge measurement; power frequency; power transformer; vibration; Acceleration; Accelerometers; Condition monitoring; Dielectric measurements; Frequency measurement; Java; Partial discharge measurement; Partial discharges; Power transformers; Vibration measurement; partial discharge measurement; power transformer; vibration analysis;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Properties and Applications of Dielectric Materials, 2009. ICPADM 2009. IEEE 9th International Conference on the
Conference_Location :
Harbin
Print_ISBN :
978-1-4244-4367-3
Electronic_ISBN :
978-1-4244-4368-0
Type :
conf
DOI :
10.1109/ICPADM.2009.5252448
Filename :
5252448
Link To Document :
بازگشت