A coordination-free ground-fault relay for AC mine distribution systems
Author
Trutt, F.C. ; Rotithor, H.G. ; Kohler, J.L.
Author_Institution
Kentucky Univ., Lexington, KY, USA
fYear
1988
fDate
2-7 Oct. 1988
Firstpage
1267
Abstract
A brief review of the coordination-free, ground-fault-protection concept is presented, followed by a discussion of major design considerations. The actual design of a coordination-free relay system is then described along with laboratory test results. Based on experimental data, it is found that the coordination-free ground fault relay meets operational objectives. When tested with a commonly utilized ground check monitor, it was found that this system should be usable for projected cable lengths up to 4000 ft.<>
Keywords
distribution networks; earthing; electrical faults; mining; power system protection; relay protection; AC mine distribution systems; design; ground check monitor; ground-fault relay; power system relay protection; Laboratories; Monitoring; Power cables; Relays; System testing;