• DocumentCode
    3405587
  • Title

    Short arcs’ interrupting capability influence on the interrupting capability of three-phase VCB

  • Author

    Poluyanova, I.N. ; Skorohod, B.A.

  • Author_Institution
    IG Tavrida Electr., Sevastopol
  • Volume
    1
  • fYear
    2008
  • fDate
    15-19 Sept. 2008
  • Firstpage
    231
  • Lastpage
    234
  • Abstract
    Capability of vacuum interrupters to extinguish short arcs burned up in the vicinity of current zero has been experimentally estimated for different vacuum interrupters, range of currents (12.5 - 31.kA rms) and TRV (according 12 kV - 24 kV rated voltages). For three-phase vacuum circuit breaker in a circuit with isolated neutral it has been demonstrated that there is an influence of unsuccessful extinction of short arcs on the arc durations for the first interrupted pole and two last poles.
  • Keywords
    vacuum arcs; vacuum circuit breakers; vacuum interrupters; current 12.5 kA to 31 kA; short arcs interrupting capability; three-phase vacuum circuit breaker; vacuum interrupters; voltage 12 kV to 24 kV; Circuit breakers; Circuit testing; Contacts; Dielectrics and electrical insulation; Equivalent circuits; Interrupters; Poles and zeros; Vacuum arcs; Vacuum technology; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Discharges and Electrical Insulation in Vacuum, 2008. ISDEIV 2008. 23rd International Symposium on
  • Conference_Location
    Bucharest
  • ISSN
    1093-2941
  • Print_ISBN
    978-973-755-382-9
  • Electronic_ISBN
    1093-2941
  • Type

    conf

  • DOI
    10.1109/DEIV.2008.4676762
  • Filename
    4676762