Abstract
A series of experiments were performed in order to optimise the forced vacuum arc current commutation with the counter-pulse current method. The experiments were performed in a laboratory arrangement with parameters representatives for the low-voltage vacuum switches. The tested vacuum arc current with values 400 A and 600 A was interrupted with a counter-pulse current at falling rates from 2 A/mus up to 90 A/mus. The main measured parameters were: ion energy and residual charge after the current zero as function of the forced falling rate of the arc current. The results can be useful in modelling and design.
Keywords
vacuum arcs; vacuum switches; counter-pulse current method; diffuse vacuum arc; ion energy; low-voltage vacuum switches; plasma parameters; residual charge; Charge measurement; Current measurement; Energy measurement; Force measurement; Laboratories; Optimization methods; Plasmas; Switches; Testing; Vacuum arcs;