Voltage inversion due to UPFC presence on second circuit of double circuit transmission line causing distance relay mal-operation
Author
Kazemi, A. ; Jamali, S. ; Shateri, H.
Author_Institution
Center of Excellence for Power Syst. Autom. & Oper., Iran Univ. of Sci. & Technol., Tehran
fYear
2008
fDate
June 30 2008-July 2 2008
Firstpage
384
Lastpage
389
Abstract
This paper discusses distance relay maloperation in the presence of unified power flow controller (UPFC) on the second circuit of a double circuit transmission line. This is done by presenting the measured impedance at the relaying point in the case of UPFC presence at the near end of the second circuit. The measured impedance at the relaying point is greatly influenced in the presence of UPFC on the transmission line or even in the case of installing UPFC on the near end of the second circuit. The measured impedance at the relaying point depends on many factors including power system structural conditions, the pre-fault loading, the ground fault resistance, and UPFC structural and controlling parameters.
Keywords
earthing; load flow; power control; power transmission faults; power transmission protection; relay protection; transmission line theory; UPFC presence; control parameters; distance relay maloperation; double circuit transmission line; ground fault resistance; impedance; power system structural conditions; pre-fault loading; unified power flow controller; voltage inversion; Distributed parameter circuits; Electrical resistance measurement; Impedance measurement; Load flow; Power system relaying; Power transmission lines; Protective relaying; Relays; Transmission line measurements; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Industrial Electronics, 2008. ISIE 2008. IEEE International Symposium on
Conference_Location
Cambridge
Print_ISBN
978-1-4244-1665-3
Electronic_ISBN
978-1-4244-1666-0
Type
conf
DOI
10.1109/ISIE.2008.4676929
Filename
4676929
Link To Document