DocumentCode :
3412504
Title :
Bus-tie synchronization and load share technique in a ring bus system with multiple power inverters
Author :
Mak, Chi ; Bolster, Larry
Author_Institution :
L-3 Commun. Power Paragon Inc., Anaheim, CA
Volume :
2
fYear :
2005
fDate :
6-10 March 2005
Firstpage :
871
Abstract :
A novel synchronizing technique is applied to a ring bus configured power system, with multiple solid-state inverters, to allow the bus-tie breaker to be closed at any time. After paralleling, load sharing is magnetically controlled without electronic circuitry or software control. Compared to the traditional one-at-a-time synchronization process, this approach significantly shortens the synchronization time as well as the interconnect-signal wire length, thus improving reliability and lowering the cost. This paper discusses the principles of this synchronization and load share control technique, supported by test results
Keywords :
circuit breakers; cost reduction; frequency convertors; invertors; load regulation; bus-tie breaker; cost lowering; frequency converter; load share control technique; magnetic control; multiple power inverter; power system; reliability; ring bus system; synchronizing technique; Costs; Frequency conversion; Frequency synchronization; Inverters; Joining processes; Power system interconnection; Power system reliability; Power system transients; Solid state circuits; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Applied Power Electronics Conference and Exposition, 2005. APEC 2005. Twentieth Annual IEEE
Conference_Location :
Austin, TX
Print_ISBN :
0-7803-8975-1
Type :
conf
DOI :
10.1109/APEC.2005.1453084
Filename :
1453084
Link To Document :
بازگشت