DocumentCode
3417642
Title
Optimum mix of ground electrodes and conductive backfills to achieve a low ground resistance
Author
Eduful, George ; Cole, Joseph Ekow ; Okyere, P.Y.
Author_Institution
Electr. Co. of Ghana, Kumasi, Ghana
fYear
2009
fDate
14-16 Jan. 2009
Firstpage
140
Lastpage
145
Abstract
Based on response curves derived from field measurements, optimum number of vertical ground electrodes for grounding electrical installation is determined. On sites where the optimum number of the electrodes cannot reach a target ground resistance, a `critical resistance area concept´ with conductive backfills is used. In this study, efficiencies of local conductive backfills for reducing ground resistance are investigated. Results show that application of tyre ashes as a conductive backfills lowers ground resistance to over 80%. It is also shown that the most favourable benefit in the ground resistance improvement is to limit the backfill to four electrodes.
Keywords
ash; earth electrodes; electric resistance; tyres; electrical installation; ground resistance; local conductive backfills; on response field measurements; response curves; tyre ashes; vertical ground electrodes; Ash; Chemicals; Earth; Electric resistance; Electrodes; Grounding; Safety devices; Substations; Tires; Voltage; Conductive Backfills and Critical Resistance area; Ground electrodes; Ground resistance;
fLanguage
English
Publisher
ieee
Conference_Titel
Adaptive Science & Technology, 2009. ICAST 2009. 2nd International Conference on
Conference_Location
Accra
ISSN
0855-8906
Print_ISBN
978-1-4244-3522-7
Electronic_ISBN
0855-8906
Type
conf
DOI
10.1109/ICASTECH.2009.5409734
Filename
5409734
Link To Document