DocumentCode :
3444604
Title :
Uncertainties in the Measurement of Power Harmonics and Flicker
Author :
Budovsky, Ilya ; Hammond, Greg
Author_Institution :
National Meas. Lab., CSIRO, Lindfield, NSW
fYear :
2004
fDate :
38139
Firstpage :
88
Lastpage :
89
Abstract :
Uncertainties of a precision measurement system developed at NML for traceable calibration of three-phase instruments measuring harmonics of current up to 20 A, voltage fluctuation and flicker are discussed. The analysis shows that current and voltage harmonics up to the 99th and fluctuating voltages can be generated and measured with relative uncertainties close to 1times10-5
Keywords :
calibration; electric current measurement; flicker noise; harmonic analysis; measurement systems; measurement uncertainty; power system measurement; voltage measurement; 20 A; current harmonics; measurement uncertainty; power harmonics measurement; voltage fluctuation; voltage harmonics; Amplitude modulation; Current measurement; Delta modulation; Electrical resistance measurement; Harmonic analysis; Measurement uncertainty; Power measurement; Power system harmonics; Testing; Voltage fluctuations;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Precision Electromagnetic Measurements Digest, 2004 Conference on
Conference_Location :
London
Print_ISBN :
0-7803-8494-6
Electronic_ISBN :
0-7803-8494-6
Type :
conf
DOI :
10.1109/CPEM.2004.305454