DocumentCode
3449093
Title
Influence of power system´s harmonic voltage on on-line leakage current monitoring of MOA
Author
Wang, Yongqiang ; Lu, Fangcheng ; Li, Heming
Author_Institution
Sch. of Electr. Eng., North China Electr. Power Univ., Baoding, China
fYear
2004
fDate
1-4 Nov. 2004
Firstpage
268
Lastpage
271
Abstract
The surge arrester is an important piece of overvoltage protection equipment in substations, and the latent faults of MOA can be found by on-line resistive leakage current monitoring. It is reasonable to adopt the resistive leakage current´s first component ir and third component i3r as the metal oxide surge arrester´s indicators. These indicators can find the aging phenomenon of the metal oxide surge arrester in time. But the existence of harmonic voltages in the power system will influence the indicators´ accuracy. In this work, this influence is analyzed and an improved compensation method to separate the resistive leakage current under the existence of harmonic voltage is described. Finally, according to these methods, an on-line resistive current MOA monitoring system based on a bus-module is developed.
Keywords
arresters; computerised monitoring; leakage currents; overvoltage protection; power system harmonics; substation protection; MOA monitoring system; bus module; compensation method; latent faults; on-line leakage current monitoring; overvoltage protection equipment; power system harmonic voltages; resistive leakage current monitoring; substations; surge arrester; Aging; Arresters; Leakage current; Monitoring; Power system analysis computing; Power system harmonics; Power system protection; Substation protection; Surge protection; Voltage control;
fLanguage
English
Publisher
ieee
Conference_Titel
Computational Electromagnetics and Its Applications, 2004. Proceedings. ICCEA 2004. 2004 3rd International Conference on
Print_ISBN
0-7803-8562-4
Type
conf
DOI
10.1109/ICCEA.2004.1459343
Filename
1459343
Link To Document