• DocumentCode
    3449540
  • Title

    Measurement and Correction of No-Load Losses of Power Transformers

  • Author

    So, E. ; Arseneau, R. ; Hanique, E.

  • Author_Institution
    National Res. Council of Canada, Ottawa, Ont.
  • fYear
    2004
  • fDate
    38139
  • Firstpage
    570
  • Lastpage
    570
  • Abstract
    The paper reviews the practice of correcting the results of no-load loss measurements of large power transformers for the effect of distorted supply voltage waveforms. Data obtained during testing of large power transformers are reproduced and analyzed at the National Research Council laboratory to ensure that the proper corrected losses are determined. The instrumentation requirements for no-load loss measurements, particularly when the transformers under tests are energized line to line are discussed
  • Keywords
    error correction; loss measurement; power transformer testing; distorted supply voltage waveforms effect; large power transformers; no-load losses correction; no-load losses measurement; Councils; Distortion measurement; Energy measurement; Instruments; Laboratories; Loss measurement; Particle measurements; Power measurement; Power transformers; Testing;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Precision Electromagnetic Measurements Digest, 2004 Conference on
  • Conference_Location
    London
  • Print_ISBN
    0-7803-8494-6
  • Electronic_ISBN
    0-7803-8494-6
  • Type

    conf

  • DOI
    10.1109/CPEM.2004.305383
  • Filename
    4097377