DocumentCode :
3449669
Title :
Development of an adaptive single-pole auto-reclosure scheme for Alexandria HV transmission system
Author :
Megahed, Ashraf I. ; Jabr, Hany M. ; Abouelenin, Fathy M. ; El-Bakry, Mahmoud A.
Author_Institution :
Dept. of Electr. Eng., Alexandria Univ., Egypt
Volume :
1
fYear :
2003
fDate :
7-12 Sept. 2003
Firstpage :
309
Abstract :
Arcing faults are the most common faults that occur in the 220 kV transmission line national grid of Egypt, in the vicinity of ´Alexandria´ city. In this paper the performance of this 220 kV TL network during arcing faults is studied with the aid of the PSCAD/EMTDC program together with a specially designed arcing fault custom model incorporated in the program. Several arcing faults are simulated, and its main characteristics are studied. Based upon the simulation results, an adaptive single-pole autoreclosure scheme is developed and tested. The developed scheme is found to be efficient in distinguishing between transient and permanent faults and in case of transient faults, determine the secondary arc extinction time.
Keywords :
arcs (electric); power system CAD; power system simulation; power system transients; power transmission faults; power transmission protection; 220 kV; EMTDC; PSCAD; adaptive single-pole auto-reclosure scheme; arcing fault custom model; high voltage transmission system; permanent faults; secondary arc extinction time; transient faults; Arc discharges; Circuit faults; Cities and towns; PSCAD; Power system faults; Power system modeling; Power system simulation; Power system transients; Power transmission lines; Testing;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Transmission and Distribution Conference and Exposition, 2003 IEEE PES
Print_ISBN :
0-7803-8110-6
Type :
conf
DOI :
10.1109/TDC.2003.1335240
Filename :
1335240
Link To Document :
بازگشت