• DocumentCode
    3451808
  • Title

    Need to revise switched capacitor controls on feeders with distributed generation

  • Author

    Brady, Philip ; Dai, Chensong ; Baghzouz, Y.

  • Author_Institution
    Nevada Power Co., Las Vegas, NV, USA
  • Volume
    2
  • fYear
    2003
  • fDate
    7-12 Sept. 2003
  • Firstpage
    590
  • Abstract
    This paper addresses the need to review switched capacitor settings on radial distribution feeders prior to installing distributed generation (DG). Bringing a DG on line without conducting an analysis may result in over-voltages or capacitors switching OFF, depending of the type of controls. A simple case of a feeder with a single DG and switched capacitor with different controls is examined in detail, and is illustrated with a numerical example. The analysis alerts electric distribution engineers to review and reset capacitor switching preset values, if necessary, prior to DG installation.
  • Keywords
    capacitor switching; distributed power generation; overvoltage; power distribution control; power generation control; switched capacitor networks; voltage control; capacitor switching; distributed generation; electric distribution engineers; feeder switched capacitor controls; overvoltages; radial distribution feeders; voltage regulation; Capacitors; Character generation; Distributed control; Distributed power generation; Power generation; Power system interconnection; Power system protection; Regulators; Substations; Voltage control;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission and Distribution Conference and Exposition, 2003 IEEE PES
  • Print_ISBN
    0-7803-8110-6
  • Type

    conf

  • DOI
    10.1109/TDC.2003.1335342
  • Filename
    1335342