DocumentCode
3457831
Title
Calibration of DC current up to 600A
Author
Hong-gang, Zhao ; Xiu-zeng, Zhang ; Yue, Liu ; Lian-ying, Zheng ; Ben-xia, Zou
Author_Institution
Div. of Electr. & Quantum Metrol., Nat. Inst. of Metrol., Beijing, China
fYear
2010
fDate
13-18 June 2010
Firstpage
603
Lastpage
604
Abstract
DC large current ratio standard is developed, calibrating DC large current based on the principle of ampere-turn balance. Under the same equilibrium condition of ampere-turn, large current can be traced to the magnetic balance current, which is relatively small, easy to be calibrated. The consistency of magnetic balance current of each turn, the linearity of magnetic balance ratios and the accuracy of current transferring at the same flux should be taken into consider.
Keywords
calibration; DC current calibration; DC large current ratio standard; ampere-turn balance; magnetic balance current; Calibration; Chaos; Coils; Current transformers; Electromagnetic measurements; Linearity; Magnetic devices; Magnetic flux; Metrology; Resistors;
fLanguage
English
Publisher
ieee
Conference_Titel
Precision Electromagnetic Measurements (CPEM), 2010 Conference on
Conference_Location
Daejeon
Print_ISBN
978-1-4244-6795-2
Type
conf
DOI
10.1109/CPEM.2010.5543168
Filename
5543168
Link To Document