• DocumentCode
    3458484
  • Title

    450MVA GCT- STATCOM for stability improvement and over-voltage suppression

  • Author

    Fujii, T. ; Temma, K. ; Morishima, N. ; Akedani, T. ; Shimonosono, T. ; Harada, H.

  • Author_Institution
    Mitsubishi Electr. Corp., Amagasaki, Japan
  • fYear
    2010
  • fDate
    21-24 June 2010
  • Firstpage
    1766
  • Lastpage
    1772
  • Abstract
    The world´s largest 450MVA STATCOM using GCT(Gate Commutated Turn-off) thyristor is designed for installation plan at Toshin substation of Chubu Electric Power Co. in Japan. The main purposes of the STATCOM are improvement of the power system stability and suppression of AC over-voltage occurred after route outage fault at heavy load condition. This paper describes the determination procedure of specification requirements and a system configuration. Also this paper reports simulation results for route outage fault and line-to-ground fault at nearby location of the STATCOM. STATCOM performance is verified by these simulation results.
  • Keywords
    flexible AC transmission systems; overvoltage protection; power system stability; static VAr compensators; thyristors; STATCOM; gate commutated turn-off thyristor; overvoltage suppression; power system stability; route outage fault; stability improvement; Automatic voltage control; Stability; FACTS; Gate Commutated Turn-off thyristor; Over-Voltage suppression; STATCOM; Stability improvement;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Electronics Conference (IPEC), 2010 International
  • Conference_Location
    Sapporo
  • Print_ISBN
    978-1-4244-5394-8
  • Type

    conf

  • DOI
    10.1109/IPEC.2010.5543206
  • Filename
    5543206