• DocumentCode
    3470845
  • Title

    Robustness of distance relay with Mho characteristic against fault resistance

  • Author

    Jamali, S. ; Shateri, H.

  • Author_Institution
    Dept. of Electr. Eng., Iran Univ. of Sci. & Technol., Tehran, Iran
  • Volume
    2
  • fYear
    2004
  • fDate
    21-24 Nov. 2004
  • Firstpage
    1833
  • Abstract
    This paper discusses the maximum earth fault resistance, which can be tolerated by a distance relay with Mho characteristic. This is defined as the boundary fault resistance the relay can discriminate between in-zone and out-of-zone faults. The robustness criterion is defined on the basis of the boundary fault resistance. In order to achieve this, the related equations are first derived and then the boundary fault resistance curve is presented. The simulation results for a typical transmission system shows the effectiveness of the proposed robustness criterion for distance relays settings.
  • Keywords
    electric resistance; power system relaying; power system stability; power transmission faults; power transmission protection; relay protection; robust control; Mho characteristic; arcing faults; boundary fault resistance; distance protection; distance relay; earth fault resistance; in-zone faults; out-of-zone faults; robustness; transmission system; Circuit faults; Earth; Electrical resistance measurement; Impedance; Power system faults; Power system protection; Power system relaying; Protective relaying; Relays; Robustness;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power System Technology, 2004. PowerCon 2004. 2004 International Conference on
  • Print_ISBN
    0-7803-8610-8
  • Type

    conf

  • DOI
    10.1109/ICPST.2004.1460300
  • Filename
    1460300