Title :
Comparing transformer derating computed using the harmonic loss factor FHL and K-factor
Author :
Shun, Tao ; Xiangning, Xiao
Author_Institution :
Minist. of Educ., North China Electr. Power Univ., Beijing
Abstract :
The transformer losses will increase while it is supplying nonlinear load current. The derating measure for normal transformers is always taken to limit the temperature of windings or top-oil. In this paper, the formulations how to calculate the maximum permissible rms non-sinusoidal load current (Imax) using the harmonic loss factors FHL and K-factor were introduced. The difference of them was also reasoned and a case study illustrated the process of reasoning. The applications of these two factors were discussed too. Imax computed using FHL for normal transformer is more economical because Imax computed using K-factor is more conservative. Based on the actual monitoring data of harmonic component, K-factor is suitable for selecting right transformers in design and FHL for establishing transformers operation capability, therefore there is a harmonic loss margin when the transformers supply non-sinusoidal load.
Keywords :
harmonic analysis; power transformers; K-factor; harmonic component; harmonic loss factor; nonlinear load current; rms nonsinusoidal load current; transformer losses; ANSI standards; Aging; Current supplies; Frequency; Hydrogen; Laboratories; Monitoring; Power generation economics; Power system harmonics; Temperature; harmonics current; losses; transformer;
Conference_Titel :
Electric Utility Deregulation and Restructuring and Power Technologies, 2008. DRPT 2008. Third International Conference on
Conference_Location :
Nanjuing
Print_ISBN :
978-7-900714-13-8
Electronic_ISBN :
978-7-900714-13-8
DOI :
10.1109/DRPT.2008.4523666