DocumentCode
3473694
Title
Transient analysis of synchronous generator with stator winding faults based on starting process
Author
Ma, Hongzhong ; Li, Huamin ; Wei, Shurong ; Ju, P. ; Zhang, Limin
Author_Institution
Dept. of Electr. Eng., Hohai Univ., Nanjing
fYear
2008
fDate
6-9 April 2008
Firstpage
1927
Lastpage
1932
Abstract
Multi-loop theory is the most common and effective method used for analyzing stator winding internal faults of synchronous generators. Based on the current analysis methods, this paper modifies the existing models and introduces the motion equation of rotor into the multi-loop analysis model to describe the associated relations between main parameters (e.g. current, voltage, torque, speed of rotation) of generator. Since the starting process of motor contains abundant information, this paper analyzes the influence of internal faults to relevant parameters, during the starting process from zero to rated speed. Through analysis some conclusions can be obtained as follow: when stator winding internal faults occur, since the influence of space harmonic is stronger, electromagnetic torque is on oscillatory regime. All waves are distorted when turn-to-turn faults occur. The starting current is bigger than normal, and the current will fluctuate after stabilization. The changing trends of short circular current and neutral-point current are the same. The currents are both small when starting, then gradually decay and go stabilization after an obvious increasing. The amplitudes of currents are far bigger than every branch current of stator. After faults, the electromagnetic torque of motor changes a lot and there is still an oscillation with certain amplitudes after stabilization. More short turns would cause bigger amplitudes of oscillation.
Keywords
power generation faults; synchronous generators; transient analysis; electromagnetic torque; multi-loop analysis model; multi-loop theory; rotor motion equation; space harmonic; starting process; stator winding internal faults; synchronous generator; transient analysis; turn-to-turn faults; Equations; Information analysis; Motion analysis; Rotors; Stator windings; Synchronous generators; Synchronous motors; Torque; Transient analysis; Voltage; electric quantity; fault; speed of rotation; starting process; synchronous generator; torque;
fLanguage
English
Publisher
ieee
Conference_Titel
Electric Utility Deregulation and Restructuring and Power Technologies, 2008. DRPT 2008. Third International Conference on
Conference_Location
Nanjuing
Print_ISBN
978-7-900714-13-8
Electronic_ISBN
978-7-900714-13-8
Type
conf
DOI
10.1109/DRPT.2008.4523722
Filename
4523722
Link To Document