Title :
Research on stator winding breakage fault of large salient-pole generator
Author :
Zhang, Kanjun ; Yin, Xianggen ; Chen, Deshu ; Zhang, Zhe ; Li, Xinjing
Abstract :
Comparing with non-salient pole generator, large salient-pole generator´s stator winding has generally more branches, so the related protection performance has some difference. In the paper, the related electric quantity change and protection performance are analyzed when generator stator winding breakage fault (SWBF) occurs, and the analysis results are confirmed by the dynamic simulation experiment. The analysis and experiment results show that the protection sensitivity to large salient-pole generator SWBF decreases because of stator winding´s multi-branch parallel structure, and in all protections, only the split-phase and unit transverse differential protection could protect the SWBF in certain degree.
Keywords :
electric generators; fault simulation; machine protection; stators; electric quantity change analysis; large salient-pole generator; protection performance analysis; stator winding breakage fault; Breakdown voltage; Circuit faults; Electric breakdown; Impedance; Iron; Performance analysis; Power generation; Protection; Stator cores; Stator windings; Dynamic simulation experiment; large salient-pole generator; stator winding breakage fault;
Conference_Titel :
Electric Utility Deregulation and Restructuring and Power Technologies, 2008. DRPT 2008. Third International Conference on
Conference_Location :
Nanjuing
Print_ISBN :
978-7-900714-13-8
Electronic_ISBN :
978-7-900714-13-8
DOI :
10.1109/DRPT.2008.4523726