• DocumentCode
    3473786
  • Title

    Research on stator winding breakage fault of large salient-pole generator

  • Author

    Zhang, Kanjun ; Yin, Xianggen ; Chen, Deshu ; Zhang, Zhe ; Li, Xinjing

  • fYear
    2008
  • fDate
    6-9 April 2008
  • Firstpage
    1949
  • Lastpage
    1954
  • Abstract
    Comparing with non-salient pole generator, large salient-pole generator´s stator winding has generally more branches, so the related protection performance has some difference. In the paper, the related electric quantity change and protection performance are analyzed when generator stator winding breakage fault (SWBF) occurs, and the analysis results are confirmed by the dynamic simulation experiment. The analysis and experiment results show that the protection sensitivity to large salient-pole generator SWBF decreases because of stator winding´s multi-branch parallel structure, and in all protections, only the split-phase and unit transverse differential protection could protect the SWBF in certain degree.
  • Keywords
    electric generators; fault simulation; machine protection; stators; electric quantity change analysis; large salient-pole generator; protection performance analysis; stator winding breakage fault; Breakdown voltage; Circuit faults; Electric breakdown; Impedance; Iron; Performance analysis; Power generation; Protection; Stator cores; Stator windings; Dynamic simulation experiment; large salient-pole generator; stator winding breakage fault;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electric Utility Deregulation and Restructuring and Power Technologies, 2008. DRPT 2008. Third International Conference on
  • Conference_Location
    Nanjuing
  • Print_ISBN
    978-7-900714-13-8
  • Electronic_ISBN
    978-7-900714-13-8
  • Type

    conf

  • DOI
    10.1109/DRPT.2008.4523726
  • Filename
    4523726