• DocumentCode
    3475155
  • Title

    The research on residual voltage of asynchronous motors and its impact on power restoration

  • Author

    Xueshen, Cui ; Yulei, Yang ; Zhenhua, Zhou ; Haisen, Zhao

  • Author_Institution
    Key Lab. of Power Syst. Protection & Dynamic Security Monitoring & Control, North China Electr. Power Univ., Beijing
  • fYear
    2008
  • fDate
    6-9 April 2008
  • Firstpage
    2333
  • Lastpage
    2338
  • Abstract
    The residual voltage of asynchronous motors after AC dump(RVACD) could have result in inrush current and inrush torque when asynchronous motors were reclosed or reswitched on the alternate power source, which would have cause damage to motors or bring power source problems such as mal-operation of feeder protection and voltage sag, etc. In this paper we built the space vector based model of motors to research the RVACD so as to thoroughly analyze the varying laws of electrical qualities and magnetic field after dumping, deduce the analytical expression of residual voltage of one motor, and get the solution for the group of asynchronous motors. The inrush current and torque are presented for power source to be restored at different moment after dumping.
  • Keywords
    induction motors; torque; asynchronous motors after AC dump; feeder protection; magnetic field; power restoration; residual voltage; voltage sag; AC motors; Equations; Magnetic analysis; Magnetic fields; Mathematical model; Mathematics; Power supplies; Surge protection; Torque; Voltage fluctuations; Asynchronous Motors; Power Restoration; Residual Voltage; Space Vector;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electric Utility Deregulation and Restructuring and Power Technologies, 2008. DRPT 2008. Third International Conference on
  • Conference_Location
    Nanjuing
  • Print_ISBN
    978-7-900714-13-8
  • Electronic_ISBN
    978-7-900714-13-8
  • Type

    conf

  • DOI
    10.1109/DRPT.2008.4523801
  • Filename
    4523801