DocumentCode
3475155
Title
The research on residual voltage of asynchronous motors and its impact on power restoration
Author
Xueshen, Cui ; Yulei, Yang ; Zhenhua, Zhou ; Haisen, Zhao
Author_Institution
Key Lab. of Power Syst. Protection & Dynamic Security Monitoring & Control, North China Electr. Power Univ., Beijing
fYear
2008
fDate
6-9 April 2008
Firstpage
2333
Lastpage
2338
Abstract
The residual voltage of asynchronous motors after AC dump(RVACD) could have result in inrush current and inrush torque when asynchronous motors were reclosed or reswitched on the alternate power source, which would have cause damage to motors or bring power source problems such as mal-operation of feeder protection and voltage sag, etc. In this paper we built the space vector based model of motors to research the RVACD so as to thoroughly analyze the varying laws of electrical qualities and magnetic field after dumping, deduce the analytical expression of residual voltage of one motor, and get the solution for the group of asynchronous motors. The inrush current and torque are presented for power source to be restored at different moment after dumping.
Keywords
induction motors; torque; asynchronous motors after AC dump; feeder protection; magnetic field; power restoration; residual voltage; voltage sag; AC motors; Equations; Magnetic analysis; Magnetic fields; Mathematical model; Mathematics; Power supplies; Surge protection; Torque; Voltage fluctuations; Asynchronous Motors; Power Restoration; Residual Voltage; Space Vector;
fLanguage
English
Publisher
ieee
Conference_Titel
Electric Utility Deregulation and Restructuring and Power Technologies, 2008. DRPT 2008. Third International Conference on
Conference_Location
Nanjuing
Print_ISBN
978-7-900714-13-8
Electronic_ISBN
978-7-900714-13-8
Type
conf
DOI
10.1109/DRPT.2008.4523801
Filename
4523801
Link To Document