Proper detection and treatment of power swing to reduce the risk of blackouts
Author
Blumschein, J. ; Yelgin, Y. ; Kereit, M.
Author_Institution
SIEMENS AG, Berlin
fYear
2008
fDate
6-9 April 2008
Firstpage
2440
Lastpage
2446
Abstract
Any sudden load change in a power system, such as a fault, line switching etc. causes the system´s generators to adjust to the new condition. In that case a power swing may occur. This paper describes a zero-setting power-swing detection method that is independent of network parameters. Power swing can be detected up to 10 Hz swing frequency, also during open pole condition and during asymmetrical operation. A blocking logic prevents unselective trips by the distance protection. For unstable power swings a flexible out of step tripping function will be proposed. The coordination of power swing detection, distance protection and out of step protection provides a reliable system protection. The risk of unwanted trips and cascading effects in the power system will be reduced.
Keywords
power system faults; power system protection; asymmetrical operation; blackouts risk; distance protection; open pole condition; power swing treatment; power system; step tripping function; unwanted trips risk; zero-setting power-swing detection method; Frequency; Logic; Power generation; Power system faults; Power system protection; Power system reliability; Distance protection; Out of step; Power swing; Power system dynamic stability; Protective relaying;
fLanguage
English
Publisher
ieee
Conference_Titel
Electric Utility Deregulation and Restructuring and Power Technologies, 2008. DRPT 2008. Third International Conference on
Conference_Location
Nanjuing
Print_ISBN
978-7-900714-13-8
Electronic_ISBN
978-7-900714-13-8
Type
conf
DOI
10.1109/DRPT.2008.4523821
Filename
4523821
Link To Document