• DocumentCode
    3476912
  • Title

    Distribution single-phase tripping and reclosing: Overcoming obstacles with programmable recloser controls

  • Author

    Cheney, Robert M. ; Thorn, John T. ; Hataway, Greg

  • Author_Institution
    Alabama Power Co., AL, USA
  • fYear
    2009
  • fDate
    10-13 March 2009
  • Firstpage
    1
  • Lastpage
    10
  • Abstract
    Ever since the first ground-fault detection device was incorporated into a fault interrupting mechanism, limitations have existed as to how much sustained load unbalance could be tolerated for a given three-phase distribution feeder. All single-phase fault interruption will introduce some incremental unbalance if load is dropped. Therefore, projected peak load levels beyond the location of fault interrupting and sectionalizing devices have always been determining factors as to whether the protection device would isolate all phases or only the faulted ones. For example, fuses, being independent phase-interrupting devices, can only be used at locations where the load they interrupt will not cause unbalance above the pickup level of upline ground-fault detection equipment. Single-phase reclosers and sectionalizers must also be applied with similar consideration. Traditionally, if high load levels will be interrupted, three-phase circuit reclosers with gang-operated interrupters are used. With no choice but to use three-phase interruption on more heavily loaded feeder sections, utilities long ago accepted the fact that possibly two-thirds of the customers beyond these protection devices would have to endure unnecessary outages each time a single-phase fault occurred. However, the quest to improve reliability by minimizing the number of customers affected has renewed interest in single-phase fault interruption on three-phase distribution lines. With the relatively recent availability of microprocessor-based recloser controls designed to operate with three-phase, independent-pole operated reclosers, utilities are taking a closer look at using single-phase fault interruption in non-traditional locations. This paper will explore the possibilities opened when a programmable recloser control, monitoring current on all phases, is used to make independent trip and close decisions for each phase. Various challenges introduced with single-phase interrupting will be addressed and - solutions offered.
  • Keywords
    fault diagnosis; microprocessor chips; power distribution control; power distribution faults; power distribution lines; power distribution protection; distribution single-phase reclosing; distribution single-phase tripping; gang-operated interrupters; ground-fault detection device; microprocessor-based recloser controls; programmable recloser controls; single-phase fault interrupting mechanism; single-phase reclosers; single-phase sectionalizers; three-phase circuit reclosers; three-phase distribution feeder; three-phase distribution lines; Circuit faults; Fault detection; Fuses; Interrupters; Laboratories; Phase detection; Phase estimation; Power engineering and energy; Power system protection; Power system reliability;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Systems Conference, 2009. PSC '09.
  • Conference_Location
    Clemson, SC
  • Print_ISBN
    978-1-4244-5248-4
  • Type

    conf

  • DOI
    10.1109/PSAMP.2009.5262328
  • Filename
    5262328