• DocumentCode
    3477516
  • Title

    The impact of harmonic resonance conditions on the connection rules for large industrial installations

  • Author

    Koch, Robert ; Gumede, Nombuso

  • Author_Institution
    Eskom Holdings Limited
  • fYear
    2005
  • fDate
    11-15 July 2005
  • Firstpage
    320
  • Lastpage
    325
  • Abstract
    The impact of power system harmonics generated by customer installations and utility equipment (i.e. SVC´s and HVDC schemes) is affected by the presence of resonance conditions in the supply network. Such resonance conditions arise due to the interaction of the generally inductive network with utility capacitors, customer power factor correction capacitors, and line and cable capacitances. The management of such resonance conditions is important in ensuring that harmonic levels are managed on utility networks., and that fair emission limits are allocated to customers. This paper considers the impact of shunt capacitor resonances on the allocation of harmonic emission limits using standards such as IEEE 519:1992 and IEC 61000-3-6:1996
  • Keywords
    IEC standards; capacitance; electricity supply industry; industrial plants; installation; power apparatus; power capacitors; power factor correction; power system harmonics; IEC 61000-3-6:1996; IEEE 519:1992; cable capacitances; customer power factor correction capacitors; fair emission limits; harmonic emission limits; harmonic resonance; inductive network; installations; large industrial installations; line capacitances; power system harmonics; shunt capacitor resonances; supply network; utility capacitors; utility equipment; Capacitance; Electricity supply industry; HVDC transmission; IEC standards; Power cables; Power capacitors; Power factor correction; Power generation; Power system harmonics; Resonance;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering Society Inaugural Conference and Exposition in Africa, 2005 IEEE
  • Conference_Location
    Durban
  • Print_ISBN
    0-7803-9326-0
  • Type

    conf

  • DOI
    10.1109/PESAFR.2005.1611838
  • Filename
    1611838