Considering peak rectifier behaviour for voltage distortion calculations in power distribution systems
Author
Ghijselen, Jozef A L ; Ryckaert, Wouter R A ; Zenner, David P I ; Melkebeek, Jan A A
Author_Institution
Dept. of Electr. Energy, Syst. & Autom., Ghent Univ., Gent, Belgium
fYear
2003
fDate
4-8 May 2003
Firstpage
5
Lastpage
11
Abstract
In many cases, power system harmonic studies are performed using current source models for the considered nonlinear loads. Peak rectifier loads are known to be highly sensitive to the parameters of the power system impedance and the voltage distortion at the rectifier terminals. The line current spectrum of such rectifiers maybe corrected to account for the influence of these parameters. In this paper it is shown that the resulting current source model does not yield sufficiently accurate results when the power system is subjected to resonances.
Keywords
distribution networks; electric impedance; harmonic distortion; load (electric); power supply quality; rectifiers; transmission network calculations; line current spectrum; nonlinear loads; peak rectifier behaviour; power distribution systems; power quality; power system harmonic; power system impedance; rectifier terminals; resonances; voltage distortion calculations; Harmonic distortion; Impedance; Power distribution; Power system harmonics; Power system modeling; Power system simulation; Power system stability; Rectifiers; Resonance; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Industrial and Commercial Power Systems, 2003. 2003 IEEE Technical Conference
Print_ISBN
0-7803-7771-0
Type
conf
DOI
10.1109/ICPS.2003.1201481
Filename
1201481
Link To Document