DocumentCode :
3480389
Title :
Compensating algorithm for use with measurement type current transformers for protection
Author :
Kang, Y.C. ; Lim, U.J. ; Kang, S.H. ; Kim, Y.G.
Author_Institution :
Chonbuk Nat. Univ., Chonju
fYear :
2005
fDate :
27-30 June 2005
Firstpage :
1
Lastpage :
7
Abstract :
The requirements to avoid current transformer (CT) saturation result in impractically large CTs. This paper describes a compensating algorithm for the distorted secondary current of the CT caused by saturation. The algorithm can compensate the distorted current irrespective of the level of the remanent flux and is suitable for use with measurement type CTs for protection. A second-difference function detects when a CT first starts to saturate. At the start of first saturation, the negative value of the second-difference function corresponds to the magnetizing current; which is used in conjunction with the magnetization curve to obtain the core flux. This value is then used as an initial flux to calculate the core flux. The magnetizing current is determined by inserting the calculated core flux into the magnetization curve and added to the secondary current. The resultant compensated current is equal to the secondary referred primary current. Test results indicate that the algorithm can compensate the severely distorted currents due to the small size of measurement CTs and is not affected by the remanent flux. The paper concludes by describing the experimental test results on a small CT using a prototype compensation system based on a digital signal processor.
Keywords :
current transformers; transformer protection; current transformer saturation; distorted secondary current; magnetization curve; magnetizing current; measurement type current transformers; secondary current; Circuit faults; Current measurement; Current transformers; Distortion measurement; Fault currents; Magnetic cores; Magnetic flux; Protection; Saturation magnetization; Signal processing algorithms; Compensation; Magnetic inrush; Magnetizing current; Remanent flux; Saturation; Saturation detection;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Tech, 2005 IEEE Russia
Conference_Location :
St. Petersburg
Print_ISBN :
978-5-93208-034-4
Electronic_ISBN :
978-5-93208-034-4
Type :
conf
DOI :
10.1109/PTC.2005.4524352
Filename :
4524352
Link To Document :
بازگشت