• DocumentCode
    3480408
  • Title

    The source and damping of local (cc. 1.2 Hz) and inter area (0.02…0.6) Hz oscillations

  • Author

    Kiss, Lajos ; Zerényi, József

  • Author_Institution
    Tech. Univ. of Budapest, Budapest
  • fYear
    2005
  • fDate
    27-30 June 2005
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    Our ten years´ experience has showed that a PSS realized by first order controlling stages is not efficient in 0.02...0.6 Hz frequency domain. In addition, these instruments have a disadvantage: damping the active power oscillations are the source of reactive power oscillations, which are exported into the network. So a PSS tuned 0.25 Hz are rejected by experts of power plants. This paper describes our method, revealing the source of the cc. 0.25 Hz frequency oscillations, and damping these by using a supplementary stage installed into the turbine governor. Damping oscillations in a lower frequency range we propose an appropriate setting of the turbine Static Load Frequency characteristics.
  • Keywords
    power system stability; reactive power; active power oscillations damping; damping oscillations; interarea oscillations; power plants; turbine governor; turbine static load frequencies; Control systems; Damping; Frequency; Power generation; Power systems; Pressure control; Servomechanisms; Servomotors; Tuning; Turbines; Constructing and Tuning of PSS; Damping of active power oscillations; Excitation systems; Inter-area oscillations; Large electric systems cooperation; Power System Stabilizer (PSS); Turbine governor systems;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Tech, 2005 IEEE Russia
  • Conference_Location
    St. Petersburg
  • Print_ISBN
    978-5-93208-034-4
  • Electronic_ISBN
    978-5-93208-034-4
  • Type

    conf

  • DOI
    10.1109/PTC.2005.4524353
  • Filename
    4524353