Corrected winding eddy-current harmonic loss factor for transformers subject to nonsinusoidal load currents
Author
Elmoudi, A. ; Lehtonen, M. ; Nordman, H.
Author_Institution
Helsinki Univ. of Technol., Helsinki
fYear
2005
fDate
27-30 June 2005
Firstpage
1
Lastpage
6
Abstract
The assumption that the transformer windings eddy loss rise in proportion to the square of the harmonic order is reasonable for small conductors and low harmonics with errors on the conservative side only for a combination of large conductors and higher harmonics. This paper presents a corrected harmonic loss factor by taking into account the depth of penetration, which leads to more accurate estimation of the increased transformer winding losses under non-sinusoidal load currents.
Keywords
eddy current losses; power system harmonics; transformer windings; eddy-current harmonic loss factor; nonsinusoidal load currents; transformer windings; transformers; Clamps; Conductors; Eddy currents; Frequency; Impedance; Phase locked loops; Power system harmonics; Temperature; Transformer cores; Windings; Harmonic loss factor; IEEE C57-110-98; Transformers;