Title :
A study of synchronized sampling based fault location algorithm performance under power swing and out-of-step conditions
Author :
Zhang, Nan ; Kezunovic, Mladen
Author_Institution :
Texas A&M Univ., College Station
Abstract :
Relay misoperations play an important role in cascading blackouts. Power swing and out-of-step conditions caused by large disturbances in the system may result in relay misoperations. This effect is analyzed and simulated in this paper. Synchronized sampling based fault location (SSFL) algorithm was proposed as part of an advanced fault analysis tool to give precise fault information and verify relay judgments. This paper further analyzes the algorithm under power swing and out-of-step conditions and tests it by both static and dynamic scenarios generated in ATP. The test results indicate that SSFL algorithm performs better than distance relay under power swing and out-of-step conditions and can be used as a robust fault analysis tool for practical use.
Keywords :
fault location; power system protection; power system relaying; advanced fault analysis tool; cascading blackouts; fault information; out-of-step conditions; power swing; relay misoperations play; robust fault analysis tool; synchronized sampling based fault location algorithm performance; Algorithm design and analysis; Analytical models; Fault location; Information analysis; Power generation; Power system faults; Power system protection; Power system relaying; Sampling methods; Testing; fault diagnosis; fault location; out-of-step; power swing; power system faults; power system protection; protective relaying; synchronized sampling;
Conference_Titel :
Power Tech, 2005 IEEE Russia
Conference_Location :
St. Petersburg
Print_ISBN :
978-5-93208-034-4
Electronic_ISBN :
978-5-93208-034-4
DOI :
10.1109/PTC.2005.4524595