Title :
Earth surface voltages at a grounding system of buried grid and rods from the fast Galerkin´s moment method
Author :
Chow, Y.L. ; Elsherbiny, M.M. ; Salama, M.M.A.
Author_Institution :
Dept. of Electr. & Comput. Eng., Waterloo Univ., Ont., Canada
Abstract :
The fast Galerkin´s moment method is used to calculate the resistance and the surface voltages of power network grounding systems which consist of a grid and rodbed. Each conductor in the grounding system is considered as one segment. The outgoing current from each conductor is assumed to be uniform along the conductor. The accuracy of the resistance calculation is very high. However, for surface voltage calculations, the voltage at the boundary has to be satisfied to yield high accuracy. In the present paper, the authors have proved that no more than two extra segments at the end of each conductor are needed to correct for the assumed current distribution. This modification yielded accurate surface voltage, with average error <5%
Keywords :
Galerkin method; current distribution; earthing; electric resistance; power system protection; calculation accuracy; current distribution; earth surface voltage; fast Galerkin´s moment method; grid; grounding systems; outgoing current; power network protection; resistance; rodbed; Conductors; Current distribution; Design methodology; Design optimization; Grid computing; Grounding; Iterative methods; Moment methods; Surface resistance; Voltage;
Conference_Titel :
Electrical and Computer Engineering, 1995. Canadian Conference on
Conference_Location :
Montreal, Que.
Print_ISBN :
0-7803-2766-7
DOI :
10.1109/CCECE.1995.526292