DocumentCode :
3486204
Title :
Analysis of the harmonic resonance during energizing the primary restorative transmission systems
Author :
Lee, H.J. ; Lee, K.S. ; Park, S.M. ; Bae, J.C. ; Song, I.J.
Author_Institution :
Kwangwoon Univ., Seoul
fYear :
2005
fDate :
27-30 June 2005
Firstpage :
1
Lastpage :
5
Abstract :
Power system restoration following a massive or complete blackout starts with energizing primary restorative transmission systems. During this primary restoration process, unexpected over-voltage may happen due to nonlinear interaction between the unloaded transformer and the transmission system. This is known as the harmonic resonance phenomenon that may cause burning out of transformer or other devices. By now the harmonic resonance has been reported in some extra high voltage systems. This paper reports the possible existence of the harmonic resonance in Korean power system. Analysis of the harmonic over-voltage is presented based on various PSCAD/EMTDC simulations.
Keywords :
overvoltage; power system CAD; power system restoration; power transformers; power transmission; EMTDC; Korean power system; PSCAD; harmonic overvoltage; harmonic resonance; harmonic resonance analysis; nonlinear interaction; power system restoration; primary restorative transmission systems; unloaded transformer; Circuit faults; Harmonic analysis; PSCAD; Power generation; Power system harmonics; Power system restoration; Power system transients; Power transmission lines; Resonance; Surge protection; Harmonic Resonance; Over-voltage; Power System Restoration;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Tech, 2005 IEEE Russia
Conference_Location :
St. Petersburg
Print_ISBN :
978-5-93208-034-4
Electronic_ISBN :
978-5-93208-034-4
Type :
conf
DOI :
10.1109/PTC.2005.4524656
Filename :
4524656
Link To Document :
بازگشت