    Power frequency electric fields at a 400 kV substation

  • Author

    Isokorpi, J. ; Keikko, T. ; Korpinen, L.

  • Author_Institution
    Dept. of Electr. Power Eng., Tampere Univ. of Technol., Finland
  • Volume
    2
  • fYear
    1999
  • fDate
    1999
  • Firstpage
    107
  • Abstract
    Measurements of electric fields have increased because of public concern about their health effects. The aim of this paper is to study electric fields at a 400 kV substation to find out whether they exceed occupational exposure guidelines, 10 kV/m, by International Commission on Non-Ionizing Radiation Protection (ICNIRP). The 400 kV switchyard of the substation had two power transformer feeders and four outgoing transmission line feeders. The electric fields were measured on the switchyard of the substation. Measurements were carried out at 1 m height along four straight lines (n=251). The voltages in the busbars were also recorded during the measurements. The highest measured electric field was 9.9 kV/m. This value does not exceed the occupational exposure level for electric fields by ICNIRP
  • Keywords
    substations; 400 kV; International Commission on Non-Ionizing Radiation Protection; busbars; electric field measurement; health effects; outgoing transmission line feeders; power frequency electric fields; power transformer feeders; substation; substation switchyard;