• DocumentCode
    3487015
  • Title

    A computer-controlled system for calibrating high voltage revenue metering systems under actual operating conditions of high voltage and sinusoidal/non-sinusoidal voltage and current waveforms

  • Author

    So, E. ; Arseneau, R. ; Bennett, D. ; Frigault, M.

  • Author_Institution
    Inst. for Nat. Meas. Stand., Nat. Res. Council of Canada, Ottawa, ON, Canada
  • fYear
    2010
  • fDate
    13-18 June 2010
  • Firstpage
    567
  • Lastpage
    568
  • Abstract
    The development of a computer-controlled system for the calibration of high voltage revenue metering systems under actual operating conditions of high voltage and sinusoidal/non-sinusoidal voltage and current waveforms will be described. Measurements can be made at any power factor from zero lag through unity, at voltages up to 100 kV line-to-ground voltage and currents up to 2000 A. The magnitude and phase uncertainties (k=2) are estimated to be not more than 50 μW/VA and 50 μrad, and 100 μW/VA and 100 μrad for sinusoidal and non-sinusoidal conditions, respectively.
  • Keywords
    calibration; control engineering computing; metering; power engineering computing; calibration; computer-controlled system; current 2000 A; high voltage revenue metering systems; high voltage sinusoidal current waveforms; high voltage sinusoidal voltage waveforms; voltage 100 kV; Calibration; Councils; Electricity supply industry deregulation; Electromagnetic measurements; Measurement standards; Phase estimation; Power generation economics; Power measurement; Power system economics; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Precision Electromagnetic Measurements (CPEM), 2010 Conference on
  • Conference_Location
    Daejeon
  • Print_ISBN
    978-1-4244-6795-2
  • Type

    conf

  • DOI
    10.1109/CPEM.2010.5544827
  • Filename
    5544827