DocumentCode :
3490496
Title :
THD reduction with grid synchronized inverter’s power injection of renewable sources
Author :
Görbe, Péter ; Magyar, Attila ; Hangos, Katalin M.
Author_Institution :
Dept. of Electr. Eng. & Inf. Syst., Univ. of Pannonia, Veszprém, Hungary
fYear :
2010
fDate :
14-16 June 2010
Firstpage :
1381
Lastpage :
1386
Abstract :
A control method for small domestic power plants using renewable energy is described in this paper. This method is not only capable of optimizing the working point of the plant but also implements active power factor correction and lowers the extant harmonic distortion in the line. The novel element in the proposed complex controller structure is the upper harmonic controller that minimizes the amplitudes of the 3rd, 5th 7th, 9th, and the 11th upper harmonic component in the output voltage. The proposed controller has been investigated by simulation in Matlab environment, and as a result, substantial improvement of the output voltage and current waveform could be achieved. Robustness of the method against nonlinear loads has also been tested.
Keywords :
harmonic distortion; harmonics suppression; invertors; power factor correction; power generation control; power grids; power plants; power system harmonics; THD reduction; active power factor correction; domestic power plants; grid synchronized inverter power injection; harmonic controller; harmonic distortion; renewable sources; Costs; Harmonic distortion; Inverters; Nonlinear distortion; Power factor correction; Power generation; Power supplies; Robustness; Solar power generation; Voltage control; nonlinear distortion; power quality; simulation; solar power generation;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Electronics Electrical Drives Automation and Motion (SPEEDAM), 2010 International Symposium on