Abstract :
The paper proposes a novel method of current detection for an active power filter and power system, which is based on a generalized dqk coordinate transform. The so-called dgk generalized coordinate is defined as the coordinate frame rotated at the angle frequency kω of the kth harmonic current. This method can effectively and accurately detect the fundamental current, its active and reactive components and any term harmonic current component of a three-phase circuit. Simulation results are carried out to verify the method of current detection.
Keywords :
active filters; harmonic distortion; power harmonic filters; power system faults; power system harmonics; power system protection; active component; active power filter; angle frequency; fundamental current; generalized dqk coordinate transform; harmonic current component; harmonic current detection technique; power system fault protection; reactive component; simulation; three-phase circuit;