DocumentCode :
3492163
Title :
Accelerated aging of 15 kV cable insulated with standard and tree retardant XLPE
Author :
Aivaliotis, S.K. ; Chan, J.C. ; Hartley, M.D.
Author_Institution :
Canada Wire & Cable Ltd., Toronto, Ont., Canada
fYear :
1988
fDate :
16-20 Oct 1988
Firstpage :
167
Lastpage :
172
Abstract :
The evaluation of commercially available standard and TR-XLPE (tree-retardant cross-linked polyethylene) to the 1987 standard was carried out. The results have been compared to accelerated aging data obtained from miniature cable tests and from extensive full-size cable tests based on the 1982 standard. It was demonstrated that the commercial TR-XLPE insulation exhibited a greater resistance to electrical voltage than the standard XLPE as evidenced by its higher retention of breakdown voltage with aging. Significantly fewer and smaller bow-tie trees were observed in the TR-XLPE. There appeared to be no significant difference in vented tree growth in the two materials
Keywords :
ageing; electric breakdown of solids; high-voltage engineering; insulation testing; life testing; organic insulating materials; polymers; power cables; 15 kV; 1982 standard; 1987 standard; accelerated aging; bow-tie trees; breakdown voltage; cross-linked polyethylene; electric breakdown; miniature cable tests; tree growth; tree retardant XLPE; Accelerated aging; Cable insulation; Cable shielding; Communication cables; Conducting materials; Insulation testing; Retardants; Temperature; Trees - insulation; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation and Dielectric Phenomena, 1988. Annual Report., Conference on
Conference_Location :
Ottawa, Ont.
Type :
conf
DOI :
10.1109/CEIDP.1988.26327
Filename :
26327