DocumentCode :
3495618
Title :
APF for harmonic voltage resonance suppression in distribution system
Author :
Sun, Xiaofeng ; Zeng, Jian ; Chen, Zhe
Author_Institution :
Key Lab. of Power Electron. for Energy Conservation & Motor Drive of Hebei Province, Yanshan Univ., Qinhuangdao, China
fYear :
2010
fDate :
16-18 June 2010
Firstpage :
818
Lastpage :
822
Abstract :
Traditional active power filter (APF) can prevent harmonic current from injecting into power system, but can not damp harmonic propagation in distribution system whereas voltage detection can do. This paper proposes a compound control method of APF based on detection of load current and harmonic voltage at the point of installation. In addition, based on the relationship between the rated volt-ampere of APF and the load volt-ampere, the conductance value could automatic adjustment. The objective of the shunt active filter is not only to compensate the harmonic but also to damp the harmonic. When the rated volt-ampere is limit, the harmonic compensation is prior considered. Computer simulation and experiment result are performed to verify the validity and effectiveness of the shunt active filter equipped with the compound control.
Keywords :
Active filters; Compounds; Harmonic analysis; Integrated circuits; Power harmonic filters; Voltage control; APF; auto gain adjustment; compound control; harmonic resonance;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Electronics for Distributed Generation Systems (PEDG), 2010 2nd IEEE International Symposium on
Conference_Location :
Hefei, China
Print_ISBN :
978-1-4244-5669-7
Type :
conf
DOI :
10.1109/PEDG.2010.5545822
Filename :
5545822
Link To Document :
بازگشت