• DocumentCode
    3496128
  • Title

    On site dynamic testing of the power swing blocking element in distance relay

  • Author

    Abu Bakar, Abdul Halim

  • Author_Institution
    Dept. of Asset Maintenance, Tenaga Nasional Berhad, Malaysia
  • fYear
    2004
  • fDate
    29-30 Nov. 2004
  • Firstpage
    158
  • Lastpage
    164
  • Abstract
    Power systems are subjected to a wide range of small and large disturbances during operation. The power system must adjust to these changing conditions and continue to operate satisfactorily and within the desired bounds of voltage and frequency. The power system should be designed to survive disturbances such as double circuit faults and lost of a large generator. Recently Peninsular Malaysia experienced a major system disturbance in the north resulting in a partial blackout. This paper describes the investigation carried out pertaining to the operation of power swing blocking element in distance relay which is the cause of the major disturbance .On site dynamic testing of the power swing blocking element was performed by using the OMICRON advanced transplay module.
  • Keywords
    power system faults; power system relaying; relay protection; testing; OMICRON advanced transplay module; distance relay; double circuit faults; dynamic testing; partial blackout; power swing blocking element; system disturbance; Circuit faults; Frequency; Performance evaluation; Power generation; Power system dynamics; Power system faults; Power system relaying; Protective relaying; Testing; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Conference, 2004. PECon 2004. Proceedings. National
  • Print_ISBN
    0-7803-8724-4
  • Type

    conf

  • DOI
    10.1109/PECON.2004.1461635
  • Filename
    1461635