Uniform field breakdown in SF6 gas at high pressures under lightning and switching surge voltages
Author
Manjunath, B.S. ; Dwarakanath, K. ; Sastry, K. S Arunachala ; Ravi, K.N.
Author_Institution
Central Power Res. Inst., Bangalore, India
fYear
1988
fDate
16-20 Oct 1988
Firstpage
329
Lastpage
333
Abstract
Experiments were conducted to determine the 50% flashover voltages (V 50) over the pressure range of 0.14 to 0.45 MPa absolute, using lightning (1.2/50 μs) and switching (100/2500 μs) impulse voltages, under uniform electric fields having two electrodes of Rogowski profile, with a gap spacing varying from 4 to 30 mm. Results indicate that the breakdown strength of SF6 gas exhibits slight saturation at higher pressures (above 0.3 MPa). The effect is higher for switching surge voltages than for impulse voltages. The polarity effect is observed both under lightning and switching surge voltages and is more pronounced at higher gas pressures and larger gap spacings. The V 50 values with switching surge voltages are generally lower than the corresponding lightning impulse voltage values
Keywords
electric breakdown of gases; flashover; gaseous insulation; impulse testing; insulation testing; lightning; sulphur compounds; surges; 0.14 to 0.45 MPa; SF6 gas; breakdown strength; flashover voltages; gap spacing; lightning impulse; polarity effect; switching surge; uniform electric fields; Breakdown voltage; Electric breakdown; Electrodes; Insulators; Ionization; Lightning; Shape control; Shape measurement; Sulfur hexafluoride; Surges;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation and Dielectric Phenomena, 1988. Annual Report., Conference on
Conference_Location
Ottawa, Ont.
Type
conf
DOI
10.1109/CEIDP.1988.26353
Filename
26353
Link To Document