DocumentCode :
3497647
Title :
XIPD testing of a 275 kV cable joint insulator
Author :
Braun, J.M. ; Fujimoto, N. ; Rizzetto, S. ; Watanabe, K. ; Niinobe, H. ; Kikuta, N.
Author_Institution :
Ontario Hydro, Toronto, Ont., Canada
Volume :
5
fYear :
1999
fDate :
1999
Firstpage :
120
Abstract :
Diagnostic tests were performed on a 275 kV prefabricated cable joint insulator using a new test technology, the X-ray induced partial discharge (XIPD) test system developed at Ontario Hydro Technologies. Special shields were designed to facilitate the evaluation of PD characteristics of the large epoxy casting. The test chamber was PD free to 600 kV; discharges from controlled voids inserted near the conductor were readily detected. A PD sensitivity of 0.08 pC was achieved during testing at up to 600 kV. The cable joint insulator remained PD free under X-ray irradiation to the target test voltage of 420 kV
Keywords :
power cable insulation; 275 kV; 420 kV; 600 kV; PD sensitivity; X-ray induced partial discharge testing; X-ray irradiation; XIPD testing; controlled voids; diagnostic tests; epoxy casting; insulation breakdown tests; power cable joint insulator; test chamber;
fLanguage :
English
Publisher :
iet
Conference_Titel :
High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)
Conference_Location :
London
ISSN :
0537-9989
Print_ISBN :
0-85296-719-5
Type :
conf
DOI :
10.1049/cp:19990900
Filename :
818252
Link To Document :
بازگشت