DocumentCode
350189
Title
Calculation of positive static breakdown voltage in rod gaps in SF 6
Author
El-Bahy, M.M.
Author_Institution
Dept. of Electr. Eng., Zagazig Univ., Egypt
Volume
3
fYear
1999
fDate
1999
Firstpage
256
Abstract
The peculiar variation of breakdown voltage Vb with pressure p in compressed SF6 due to corona stabilization of the applied field is well pronounced in rod to plane gaps. In this paper, the space-charge modified field has been calculated and a simple criterion based on the gap minimum field is proposed for breakdown in the rising straight part of the Vb-p characteristic. This calls at first for assessment of the corona onset voltage. For pressures greater than the critical pressure breakdown occurs without any preceding corona discharges and the breakdown voltage is theoretically predicted. The calculated corona-onset Vo and breakdown voltages agreed with those measured experimentally within ±10%
Keywords
SF6 insulation; SF6; applied field; breakdown voltage; compressed SF6; corona discharges; corona onset voltage; corona stabilization; critical pressure; gas pressure; positive static breakdown voltage; rod gaps; space-charge modified field;
fLanguage
English
Publisher
iet
Conference_Titel
High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)
Conference_Location
London
ISSN
0537-9989
Print_ISBN
0-85296-719-5
Type
conf
DOI
10.1049/cp:19990748
Filename
816769