• DocumentCode
    350189
  • Title

    Calculation of positive static breakdown voltage in rod gaps in SF 6

  • Author

    El-Bahy, M.M.

  • Author_Institution
    Dept. of Electr. Eng., Zagazig Univ., Egypt
  • Volume
    3
  • fYear
    1999
  • fDate
    1999
  • Firstpage
    256
  • Abstract
    The peculiar variation of breakdown voltage Vb with pressure p in compressed SF6 due to corona stabilization of the applied field is well pronounced in rod to plane gaps. In this paper, the space-charge modified field has been calculated and a simple criterion based on the gap minimum field is proposed for breakdown in the rising straight part of the Vb-p characteristic. This calls at first for assessment of the corona onset voltage. For pressures greater than the critical pressure breakdown occurs without any preceding corona discharges and the breakdown voltage is theoretically predicted. The calculated corona-onset Vo and breakdown voltages agreed with those measured experimentally within ±10%
  • Keywords
    SF6 insulation; SF6; applied field; breakdown voltage; compressed SF6; corona discharges; corona onset voltage; corona stabilization; critical pressure; gas pressure; positive static breakdown voltage; rod gaps; space-charge modified field;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)
  • Conference_Location
    London
  • ISSN
    0537-9989
  • Print_ISBN
    0-85296-719-5
  • Type

    conf

  • DOI
    10.1049/cp:19990748
  • Filename
    816769