DocumentCode
3503853
Title
PFC correcting of single-inductor three-level bridgeless with one-cycle
Author
Qingjiang Yang ; Hongyang Liu
Author_Institution
Coll. of Electr. & Inf. Eng., Heilongjiang Inst. of Sci. & Technol., Harbin, China
Volume
02
fYear
2013
fDate
16-18 Aug. 2013
Firstpage
1279
Lastpage
1282
Abstract
To improve the power factor of inverter or UPS and restrain the input current harmonic, a one-cycle control technology is applied to a single inductor three-level bridgeless boost power factor correction circuit in this paper, analyzing the single cycle control mode and principle of charging and discharging, building the simulink model of one-cycle controlling single-inductor three-level bridgeless boost circuit. The results show that the one-cycle control can restrain the harmonic of the input current, the total harmonic distortion rate is 0.1, and the input power factor is 0.995.
Keywords
harmonic distortion; invertors; power conversion harmonics; power factor correction; power inductors; uninterruptible power supplies; PFC correction; Simulink model; UPS power factor improvement; charging principle; discharging charging; input current harmonic; input power factor; inverter power factor improvement; one-cycle control technology; one-cycle controlling single-inductor three-level bridgeless boost circuit; single cycle control mode; total harmonic distortion rate; DSL; Reactive power; Software packages; PFC; one-cycle control; three-level bridgeless;
fLanguage
English
Publisher
ieee
Conference_Titel
Measurement, Information and Control (ICMIC), 2013 International Conference on
Conference_Location
Harbin
Print_ISBN
978-1-4799-1390-9
Type
conf
DOI
10.1109/MIC.2013.6758193
Filename
6758193