DocumentCode
350429
Title
Diagnostics of high voltage metal oxide arresters procedure errors
Author
Chrzan, Klystian ; Koehler, Wolfgang
Author_Institution
Wroclaw Univ. of Technol., Poland
Volume
2
fYear
1999
fDate
1999
Firstpage
385
Abstract
A technique has been described which can determine AC resistive current directly or by obtaining the watt loss of the test specimen and dividing by the true RMS (trms) value of the applied voltage. The procedure errors with standard voltage dividers and digital systems have been calculated. Special attention was paid to the voltage shift. A new method for the direct resistive current measurement was proposed. The effect of the small amount of harmonics was shown
Keywords
arresters; AC resistive current; applied voltage true RMS; digital systems; direct resistive current measurement; harmonics; high voltage metal oxide arresters; procedure errors diagnosis; voltage shift; watt loss;
fLanguage
English
Publisher
iet
Conference_Titel
High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)