Title :
Stability enhancement of wind farm integrated power system during unsuccessful reclosing of circuit breakers
Author :
Sheikh, M.R.I. ; Mondol, N.
Author_Institution :
EEE Dept., Rajshahi Univ. of Eng. & Technol., Rajshahi, Bangladesh
Abstract :
This paper aims at investigating the effect of the Voltage Source Converter (VSC) controlled Superconducting Magnetic Energy Storage (SMES) on the transient stability enhancement of a fixed speed wind generator during unsuccessful reclosing of circuit breakers. The control scheme of SMES based on a pulse width modulation based voltage source converter (PWM-VSC) and a two-quadrant DC-DC chopper using Insulated Gate turn off Bipolar Transistor (IGBT). Simulation results of symmetrical and unsymmetrical faults at wind farm terminal bus show that the proposed controlled SMES is able to stabilize the system well in case of an unsuccessful reclosing of circuit breakers.
Keywords :
PWM power convertors; circuit breakers; electric generators; insulated gate bipolar transistors; power generation faults; power system transient stability; superconducting magnet energy storage; wind power plants; IGBT; PWM-VSC; VSC controlled superconducting magnetic energy storage; circuit breakers; fixed speed wind generator; insulated gate turn off bipolar transistor; pulse width modulation based voltage source converter; transient stability enhancement; two-quadrant DC-DC chopper; wind farm integrated power system; wind farm terminal bus faults; Choppers (circuits); Circuit breakers; Coils; Generators; Magnetic analysis; Magnetic circuits; Superconducting magnetic energy storage; superconducting magnetic energy storage (SMES) unit; transient stability enhancement; unsuccessful reclosing; voltage source converter (VSC) and DC-DC chopper;
Conference_Titel :
Informatics, Electronics & Vision (ICIEV), 2012 International Conference on
Conference_Location :
Dhaka
Print_ISBN :
978-1-4673-1153-3
DOI :
10.1109/ICIEV.2012.6317405