DocumentCode :
3510106
Title :
Polymer surge arresters: Degradation versus electrical performance
Author :
Silva, David A. ; M. Costa, Eduardo ; Franco, J.L. ; Abreu, S.R. ; Jesus, R.C. ; Antonionni, M. ; Pissolato, Jose
Author_Institution :
High Voltage Lab., Univ. of Campinas - Unicamp, Sao Paulo, Brazil
fYear :
2012
fDate :
10-12 Oct. 2012
Firstpage :
63
Lastpage :
68
Abstract :
This research presents the electrical performance of metal-oxide surge arresters with polymeric housing, applied on the power distribution network, as a function of the physical-chemical degradation which over the time they are exposed. The surge arresters are submitted to an immersion test/aging in water with sodium chloride at 90°C for three months, in order to simulate about 20 years of field application. The surge arresters based on periodical measurements of the leakage current are evaluated.
Keywords :
arresters; distribution networks; leakage currents; polymers; electrical performance; immersion test-aging; leakage current; metal-oxide surge arresters; periodical measurements; physical-chemical degradation; polymer surge arresters; polymeric housing; power distribution network; temperature 90 degC; Aging; Arresters; Current measurement; Leakage current; Polymers; Surges; leakage current; metal-oxide varistor; polymer-housed arresters; water immersion;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Power and Energy Conference (EPEC), 2012 IEEE
Conference_Location :
London, ON
Print_ISBN :
978-1-4673-2081-8
Electronic_ISBN :
978-1-4673-2079-5
Type :
conf
DOI :
10.1109/EPEC.2012.6474981
Filename :
6474981
Link To Document :