    Experience in the Detection of High Impedance Faults in the Line Macagua-Callao-Claritas 400 kV

  • Author

    Malave, M. ; Bermudez, O. ; Acevedo, V.

  • Author_Institution
    Protections & Meas. Sect., EDELCA
  • fYear
    2006
  • fDate
    15-18 Aug. 2006
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    On day 28-03-02 at 12:37, line Macagua-Callao-Claritas 400 kV tripped, additionally the autotransformer 1 400/230 kV, the reactances 1 and 2 of 50 MVAr of the Claritas substation, and the transformers 230/69/13.8 kV in Boa Vista substation tripped too. According to the carried out analysis, a fault of high resistance was detected in the phase "A" of the line Macagua-Claritas, near to Claritas substation, which was not detected by the distance protections of the line, this fault should be cleared by the high impedance protections in 200 ms. This scheme did not operate because the relays of the Macagua end did not detect the fault and they did not send the signals of high frequency to the end of Claritas to complete its performance. Finally the fault was cleared in 4.4 sec. by the relay of high impedance (67N) in their back-up scheme. All the other equipments (transformers and reactors) that were tripped by correct performance of the ground overcurrent protection in back-up for the fault duration. This work explains the behavior of the power system and the protections equipments for the fault in reference, additionally some proposals of improvements are indicated to achieve a better performance of the protections devices
  • Keywords
    autotransformers; overcurrent protection; power system interconnection; power transmission faults; power transmission lines; power transmission protection; relay protection; substations; 13.8 kV; 230 kV; 4.4 sec; 400 kV; 69 kV; Boa Vista substation; Claritas substation; Macagua-Callao-Claritas line; autotransformer; back-up scheme; distance protections; ground overcurrent protection; high impedance faults detection; high impedance protections; Fault detection; Frequency; Impedance; Inductors; Phase detection; Power system protection; Power system relaying; Protective relaying; Substation protection; Transformers; Directional Protection; Fault to Ground; High Impedance Protections; Transmission Line;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission & Distribution Conference and Exposition: Latin America, 2006. TDC '06. IEEE/PES
  • Conference_Location
    Caracas
  • Print_ISBN
    1-4244-0287-5
  • Electronic_ISBN
    1-4244-0288-3
  • Type

    conf

  • DOI
    10.1109/TDCLA.2006.311583
  • Filename
    4104514