DocumentCode :
351190
Title :
Performance and calibration of high-end impulse analysing systems
Author :
Loppacher, M. ; Walder, L.
Author_Institution :
Haefely Trench AG, Basel, Switzerland
Volume :
1
fYear :
1999
fDate :
1999
Firstpage :
177
Abstract :
High-end digital impulse analysing systems are becoming more and more accurate and surpass the relevant standard. Various performance data such as amplitude resolution and sampling rate are carefully checked for their influence on final accuracy or improvements in connection with sophisticated signal processing. As important as technical performance are frequent calibrations, which are also influenced by the quality standard ISO 9000. However, frequent calibrations are an expensive procedure. To minimise cost and work, a unique channel insert system has been developed. This channel insert system allows for an easy calibration procedure and a continuous device availability at 60% of the cost of conventional continuously operational systems
Keywords :
impulse testing; ISO 9000 quality standard; amplitude resolution; calibration; channel insert system; continuous device availability; high-end digital impulse analysing systems; measurement performance; sampling rate; signal processing; technical performance;
fLanguage :
English
Publisher :
iet
Conference_Titel :
High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)
Conference_Location :
London
ISSN :
0537-9989
Print_ISBN :
0-85296-719-5
Type :
conf
DOI :
10.1049/cp:19990536
Filename :
820373
Link To Document :