DocumentCode
351192
Title
Winding slackness monitoring as a diagnostic for insulation ageing in oil-paper insulated power transformers
Author
De Klerk, PJ ; Reynders, JP
Author_Institution
Eskom Technol. Group, South Africa
Volume
1
fYear
1999
fDate
1999
Firstpage
185
Abstract
On-line methods of monitoring ageing in oil-paper insulated power transformers are limited. In this work, the use of a novel, galvanically isolated, displacement transducer is investigated, which uses winding slackness as surrogate for ageing of the paper insulation. An experiment is described, in which paper ageing is accelerated by means of elevated temperature and ageing is monitored by dissolved gas analysis, Furan analysis and depolymerisation of the paper. These observations correlate very well with increased displacement measured in the winding on the transformer core
Keywords
power transformer insulation; Furan analysis; depolymerisation; displacement measurement; dissolved gas analysis; elevated temperature; galvanically isolated displacement transducer; insulation ageing diagnosis; oil-paper insulated power transformers; paper ageing acceleration; transformer core; winding slackness monitoring;
fLanguage
English
Publisher
iet
Conference_Titel
High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)
Conference_Location
London
ISSN
0537-9989
Print_ISBN
0-85296-719-5
Type
conf
DOI
10.1049/cp:19990538