• DocumentCode
    351192
  • Title

    Winding slackness monitoring as a diagnostic for insulation ageing in oil-paper insulated power transformers

  • Author

    De Klerk, PJ ; Reynders, JP

  • Author_Institution
    Eskom Technol. Group, South Africa
  • Volume
    1
  • fYear
    1999
  • fDate
    1999
  • Firstpage
    185
  • Abstract
    On-line methods of monitoring ageing in oil-paper insulated power transformers are limited. In this work, the use of a novel, galvanically isolated, displacement transducer is investigated, which uses winding slackness as surrogate for ageing of the paper insulation. An experiment is described, in which paper ageing is accelerated by means of elevated temperature and ageing is monitored by dissolved gas analysis, Furan analysis and depolymerisation of the paper. These observations correlate very well with increased displacement measured in the winding on the transformer core
  • Keywords
    power transformer insulation; Furan analysis; depolymerisation; displacement measurement; dissolved gas analysis; elevated temperature; galvanically isolated displacement transducer; insulation ageing diagnosis; oil-paper insulated power transformers; paper ageing acceleration; transformer core; winding slackness monitoring;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)
  • Conference_Location
    London
  • ISSN
    0537-9989
  • Print_ISBN
    0-85296-719-5
  • Type

    conf

  • DOI
    10.1049/cp:19990538
  • Filename